Actions

Difference between revisions of "Active Vent"

From Unofficial Stationeers Wiki

Line 28: Line 28:
  
 
(*) This is the reason why airlocks need an internal pressure of at least 100 kPa to work correctly. This behavior can also be inconvenient on worlds like Loulan whose atmosphere is well above 101kPa.  Manually-operated "airlocks" for greenhouses can not pump back up to Loulan atmosphere during the exit cycle.  If the pressure is already >101kPa the vent will have no effect, and if it is <101kPa the vent will stop when it reaches 101kPa.
 
(*) This is the reason why airlocks need an internal pressure of at least 100 kPa to work correctly. This behavior can also be inconvenient on worlds like Loulan whose atmosphere is well above 101kPa.  Manually-operated "airlocks" for greenhouses can not pump back up to Loulan atmosphere during the exit cycle.  If the pressure is already >101kPa the vent will have no effect, and if it is <101kPa the vent will stop when it reaches 101kPa.
 +
 +
(**) Unwanted behavior can be corrected by storing desired pressure value to 'PressureExternal' on every loop. Example:
 +
s dVentInterior PressureExternal rInteriorPressure
 +
s dVentExterior PressureExternal rExteriorPressure
  
 
To calculate the moles per tick, use the following equation:
 
To calculate the moles per tick, use the following equation:

Revision as of 19:19, 14 January 2023

Other languages:
English • ‎español
Active Vent
ItemActiveVent.png
Properties
Stacks Yes (5)
Recipe
Created With Hydraulic Pipe Bender, Fabricator
Cost 5g Iron, 1g Gold, 5g Copper
Active Vent
StructureActiveVent.png
Operation
Power Usage 100W
Construction
Placed with Kit (Active Vent)
Placed on Small Grid
Stage 1
Deconstruction
Deconstructed with Hand Drill
Item received Kit (Active Vent)


Description

Active vents use power to move gas from and to pipes and the exterior. Its functionality depends on its mode:

  • in "Outward mode" (switch in blue), the vent increases the external pressure (by moving gas from the pipes to the exterior) up to "PressureExternal", by default(*) equal to 101 kPa
  • in "Inward mode" (switch in red), the vent decreases the external pressure (by moving gas from the exterior to the pipes) down to "PressureExternal", by default(*) equal to 0 kPa

"PressureExternal" and "PressureInternal" values should be modified programmatically via IC10 scripts, as they reset to default values on mode change. Values can be set through logic chips, if the value is modified after a mode change. Switching logic chips off then on will not modify values on the active vent, the values supplied to the chips must be altered for the values to be written.

(*) This is the reason why airlocks need an internal pressure of at least 100 kPa to work correctly. This behavior can also be inconvenient on worlds like Loulan whose atmosphere is well above 101kPa. Manually-operated "airlocks" for greenhouses can not pump back up to Loulan atmosphere during the exit cycle. If the pressure is already >101kPa the vent will have no effect, and if it is <101kPa the vent will stop when it reaches 101kPa.

(**) Unwanted behavior can be corrected by storing desired pressure value to 'PressureExternal' on every loop. Example: s dVentInterior PressureExternal rInteriorPressure s dVentExterior PressureExternal rExteriorPressure

To calculate the moles per tick, use the following equation: n = (P * V) / (R * T) (These do not take into account the constraints imposed by "PressureExternal" and "PressureInternal")

Note: In order to get the proper units out of this calculation you need to either use kPa and L, or Pa and M3.

Where (Inward vent):

  • P = Min(Room pressure, 10.1325 kPa)
  • V = 8000 L
  • n = Moles per tick
  • R = Gas constant (8.3144)
  • T = Room temperature

Where (Outward vent):

  • P = Min(Pipe pressure, 10.1325 kPa)
  • V = Pipe volume in L
  • n = Moles per tick
  • R = Gas constant (8.3144)
  • T = Pipe temperature

Note: The insert slot currently takes any item and seems to have no effect.

Data Network Properties

These are all Data Network properties of this device.

Mode Values

These lists the values and meanings for the "Mode" property of the Active Vent.

Value Meaning
0 "Outward" mode (Pumping gas from the connected pipe network to the outside.)
1 "Inward" mode (Pumping gas from the outside to the connected pipe network.)
2 (Unknown)

Data Parameters

These are all parameters that can be written with a Logic Writer, Batch Writer, or Integrated Circuit (IC10).


Parameter Name Data Type Description
Open Boolean Does not function.
Mode Integer Sets the Active Vent mode to the passed setting. (See Mode Values)
PressureExternal Float Mode 0 maximum room pressure, Mode 1 minimum room pressure. Value is overwritten to 101.325 in Mode 0 and 0 in Mode 1 when mode is changed. The vent will still consume energy when pressure is reached.
PressureInternal Float Mode 0 minimum pipe pressure, Mode 1 maximum pipe pressure. Value is overwritten to 0 in Mode 0 and 50662.5 in Mode 1 when mode is changed. The vent will still consume energy when pressure is reached.
Lock Boolean Locks the Active Vent, when set to 1. Unlocks it, when set to 0.
Setting Float Does not function.
On Boolean Turns the Active Vent on, when set to 1. Turns it off, when set to 0.

Data Outputs

These are all parameters, that can be read with a Logic Reader or a Slot Reader. The outputs are listed in the order a Logic Reader's "VAR" setting cycles through them.

Output Name Data Type Description
Power Boolean Returns whether the Active Vent is receiving power and is turned on. (0 for no, 1 for yes)
Open Boolean Returns whether the Active Vent is open. (0 for no, 1 for yes) (Untested)
Mode Integer Returns the setting of the current mode of the Active Vent. (See Mode Values)
Error Boolean Returns whether the Active Vent is currently flashing an error. (0 for no, 1 for yes)
PressureExternal Float Returns the desired external pressure of the Active Vent.
PressureInternal Float Returns the desired internal pressure of the Active vent. (Untested)
Lock Boolean Returns whether the Active Vent is locked. (0 for no, 1 for yes)
Setting Float Returns a range from 0.0 to 100.0. (Assumption) Returns the percentage amount of pumping throughput of the Active Vent.
Maximum Integer Returns 100. (Assumption) Returns the maximum throughput percentage of the Active Vent.
Ratio Float Returns a range from 0.0 to 1.0. (Assumption) Returns the percentage amount of pumping throughput of the Active Vent.
On Boolean Returns whether the Active Vent is set to on. (0 for no, 1 for yes)
RequiredPower Integer Returns the current amount of power needed for the Active Vent.